Zbw series combined substation

ZBW SERIES COMBINATION TRANSFORMER SUBSTATIONGeneralTo meet requirement of urban network construction, ZBW series combination substation is designed by our company with is own advantage such as compact, complere unit, reliable and safe, convenient maintenance, artistic appearance and so on. It is applicable for the outdoor admin

Featured Products

ZBW SERIES COMBINATION TRANSFORMER SUBSTATION
General
To meet requirement of urban network construction, ZBW series combination substation is designed by our company with is own advantage such as compact, complere unit, reliable and safe, convenient maintenance, artistic appearance and so on. It is applicable for the outdoor administration of power supply such as high building, residential area, stations and wharfs, ports, factory and park.
FEATURE
1. The frame of substation is made of steel and angle iron galvanized to have the enough mechanical strength
2. Cold-rolled steel sheet, stainless steel, aluminum alloy sheet or compound colorful sheet is used for the enclosure.
3. Each cubicle is separated by steel sheet to be different shape inside
4. The illuminating devices are installed inside L. V. &H. V. Cubicles and transformer cubicle for supervision and maintenance.
5. The cover is double-layer to prevent the heat from increasing temperature.
6. Natural ventilation is taken for transformer. When the temperature inside the transformer cubicle is higher than the set temperature, the fan installed on the top will start to work and control the temperature.
7. Sealing devices are put on the turning parts to be moisture-proof.
8. Perfect protection and convenient operation, particularly "five-proof" functions on H. V. Side ensures the security of maintenance.
9. The product is good-looking and natural in certain environment
OPERATION CONDITION
Altitude: <1000m
Ambient temperature: -25º C- +40º C
Wind speed: <30m/s
Relative humidity: <90%
NoItemUnitHigh voltage apparatusTransformerLow voltage apparatus
1Rated voltage UekV7.2,126/0.4    , 10/0.40.4
2Rated capacity SekvA 200~1250 
 
3Rated current LekvA200~630 100~3000
4Rated drop out currentAswitch disconnector 400~630A 15~63
kAsubject to fuse if the combined appliance is adopted
5Rated short time withstand currentkA20(2S)200~400kvA15(1S)
12.5(4S)400kvA30(1S)
6Rated crest withstand currentkA31.5 , 50200~400kvA30
400kvA63
7Rated making currentkV31.5 , 50  
81 min power frequency withstand currentkVphase to earth phase to phase 42 , 30Oil-immersed transformer: 35/5 min≤300V when 2kV
across isolating distance 48 , 34dry type: 28/5 min300, 660v when 2.5kV
9Lightning impulse withstand currentkVphase to earth phase to phase 85 , 75 75 
phase to earth phase to phase 85 , 75 
10NoisedB Oil-immersed transformer: <55 
dry type: <65
11Protection class IP33IP23IP33
12Outline dimensionChoose different dimension according to the capacity and type of power transformer

Zbw Series Combination Transformer Substation